unit for a single point monitoring in a grounded electrical power system. The supervision unit is used with sum current transformer by a measuring cable.
APPLICATIONS OF SUPERVISION UNIT VRE-11A
Supervision of a grounded (3-phases+N+G / 3-phases+G / 1-phase+N+G) distribution power system
In a grounded distribution system the return current flows through the neutral conductor (N) back to the main ground bus. The current in the grounding (G) conductor is theoretically zero. However, in practice there is a small current in the G conductor the so called inherent leakage current. It is caused by different devices, filters and big fluorescent lamp groups connected to the electrical system. This leakage current increases if faults occur in the distribution system from insulation damages in the devices connected to the distribution system or from wiring errors in the electrical system itself. These faults may appear as faults or short circuits between the ground conductor and the power supply. It is important to detect an emerging fault and remove it quickly in order to guarantee the proper operation of the grounded electrical system. A continuous fault situation may be hazardous for the user, for the equipment connected to the electrical system as well as to the system itself (overheating arcing faults and fire risk).
Supervision of the integrity of a distribution network
Leakage and stray currents cause potential differences and disturbance voltages in computer and building management networks. These power disturbances are particularly harmful in data lines. If a partial or complete short circuit occurs between the N and G conductors, the electrical system operates as a four conductor system. In this case the benefits of a five conductor system are lost. Only by continuous supervision of a grounded electrical system can be kept "clean".
Detection of wiring errors
Wiring errors may spoil the advantages of a grounded electrical system from being achieved and cause hazards for the user. With the help of a supervision unit the wiring errors may be detected immediately. Possible wiring errors are:
- N and G conductors are connected together not only through the main ground bus
- N and G conductors have been reversed somewhere in the electrical system
- a device has been connected between a phase conductor and the ground
- a device is grounded through its installation parts.
- Neutral to neutral wiring errors (if the measurement is close to the load)
Detection of insulation deterioration
The most usual reason for a fire risk of an electrical device (cable, motors, heating systems etc.) is the damage in the cable insulation. This may occur due to overloading, excessive moisture, insulation deterioration, mechanical stress, etc. The supervision equipment detects an incipient insulation damage as the fault current value rises. The Superintend system detects an arcing fault before a fuse or a circuit breaker operates.
Measurement of small currents
With this supervision unit it is possible to measure small currents in the range of 1 mA to 10 A
On-line monitoring of electrical insulation
Over time leakage current increases because the insulation begins to degrade. By continuous monitoring of leakage current, weakened insulation can be identified before the circuit breaker trips and production is shut down.
MONITORING WITH A RECORDER

AC output for a recorder
1mVAC = 1mAAC
VRE-11 reading 1mA-2.5A
VRE-11/100 reading 10mA-25A
ANALOG OUTPUT

Voltage output in the range 10mA-10A
The thick line corresponds the analog output voltage measures in the VRE-11A.
A linear voltage output is gained when the current is below 2.5A.
DISPLAY
| ALARM DISPLAY |
 |
Alarm limit has been exceeded.
The duration of the alarm has been shorter than the set delay.
|
 |
Current alarm.
The duration of the alarm has been longer than the set delay.
|
 |
Equipment fault.
The faults can be scrolled in the fault record.
|
| MIN/MAX CURRENT MEMORY |
 |
Display of max current (491mA).
|
 |
Display of min current (97mA).
|
|
Max/min current memories can be reset. Active equipment faults stay in memory until the fault has been fixed and acknowledged.
|
AN EXAMPLE OF WIRING

CONNECTIONS OF VRE-11A

Terminal connections of Superintend VRE-11A
INTERCONNECTION CABLES
WIRING WITH STANDARD PLUG-IN MEASURING CABLES:
IN THE USA 600 V, 90°C
IN THE OTHER COUNTRIES 1000 V, 90°C

WIRING WITH INSTRUMENTATION CABLE
Installation with screw terminals
The VMPH-2F measuring cable for the current transformer is 2-feet long (0.6 m). One end of the cable has a plug connector (for VRE-11A unit) and the other end has four colour-coded wires for connection to screw terminals on the instrumentation cable.

Installation with plug-in measuring cables
The VMP-2F measuring cable for the current transformer is also two-feet long (0.6 m). Both ends of the cable have plug connectors. The VMPA-1 (one channel model) and VMPA-4 (four channel model) are adapters for VMP-2F measuring cable. The adapter has socket(s) for VMP-2F measuring cable and screw terminal(s) for the instrumentation cable.

TECHNICAL SUMMARY
|
Leakage Current Monitor VRE-11A
|
|
Operating voltage
|
USA 110...120VAC 60Hz
Other countries 230V + 10% 50 Hz
|
|
Power consumption
|
1.5VA
|
|
Operating temperature
|
+22...+122°F (-5...+50°C)
|
|
Humidity
|
< 95%, non condensed
|
|
Dimensions
|
shown on the next page
|
|
Installation
|
|
mains and the alarm relay
|
screwterminal
|
|
sum current transformer
|
4-pin modular connector
|
|
voltage output
|
Ø 0,16" (4 mm) socket (front panel)
|
|
Weight
|
VRE-11A 1 lb (450 g)
|
|
Measuring characteristics
|
|
Channel 1 pc
|
|
Measuring range
|
|
VRE-11A
|
0 - 9.99A (60Hz)
|
|
VRE-11A/100
|
0 99.9 A
|
|
Resolution
|
|
VRE-11A
|
- I < 1A 1mA
- I 1A
|
|
VRE-11A/100
|
-I < 10A 10 mA
-I > 10A 100 mA
|
|
Accuracy with
|
|
VMI
|
+5% (closed core), + 1-2 dgt
|
|
VMIK
|
+10% (split-core) , + 1-2 dgt
|
|
Setup
|
|
alarm range
|
VRE-11A
VRE-11A/100
|
10 mA - 9.5A
100 mA 95 A
|
|
alarm delay
|
|
0 - 60 s (with the minimum
delay the action time of the relay is 140 ms)
|
|
hysteresis
|
|
0 - 90% alarm level
|
|
AC-output
|
|
VRE-11A
|
correspondence
|
1mVAC = 1mAAC
|
|
linear measuring range
|
1 mA - 2.5 A
|
|
accuracy:
|
+ 5% with the VMI transformers
+10% with the VMIK transformers
|
|
VRE-11A/100
|
correspondence
|
1mVAC = 1mAAC
|
|
linear measuring range
|
10 mA - 2.5 A
|
|
accuracy:
|
+ 5% with the VMI transformers
+ 10% with the VMIK transformers
|
|
Alarm relay
|
|
relay connection
|
two potential free, change-over contactors
|
|
Imax
|
max. 5A
|
|
Vmax
|
250 V AC
|
|
Vmax
|
24 V DC
|
|
Current transformer
|
|
thermal limit current Ith/t
|
20kA/s
|
|
dynamic limit current Idyn
|
50kA
|
|
continuous thermal limit current
|
100A
|
DIMENSIONS
