VRE-10 Single Channel Monitoring Unit

1. Monitoring Unit VRE-10
2. Measuring Cable from 2 to 32 feet (1...10 m)
3. Sum Current Transformer VMI-130
USA model
- VRE-10US English (USA)

Other countries
- VRE-10E English
- VRE-10S Swedish
- VRE-10 Finnish

The Supervision Unit is connected to an appropriately-sized current transformer by measuring cable.


FEATURES OF VRE-10

DIGITAL DISPLAY OF FAULT CURRENT FROM 5 mA to 10 A

EASY SETTINGS WITH DIGITAL DISPLAY

MEASURING DISTANCE UP TO 320 FT (100 m).

SELF-TESTING OF MONITORING UNIT.
MEASURING CABLE AND SUM CURRENT TRANSFORMER

MIN AND MAX MEMORY


APPLICATIONS OF SUPERINTEND VRE-10

Supervision of a grounded (3-phases+N+G / 3-phases+G / 1-phase+N+G) high resistance grounded distribution power system

In a grounded distribution system the return current flows through the neutral conductor (N) back to the main ground bus. The current in the grounding (G) conductor is theoretically zero. However, in actual practice there is a small current in the G conductor – the so called inherent leakage current. It is caused by different devices, filters, and big fluorescent lamp groups connected to the electrical system. This leakage current increases if faults occur in the distribution system from insulation damage in the devices connected to the distribution system or from wiring errors in the electrical system itself. These faults may appear as faults or short circuits between the ground conductor and the power supply. It is important to detect an emerging fault and remove it quickly in order to guarantee the proper operation of the grounded electrical system. A continuous fault situation may be hazardous for the user, for the equipment connected to the electrical system as well as to the system itself (overheating, arching faults and fire risk).

Detection of wiring error

Wiring error may spoil the advantages of a grounded electrical system from being achieved and cause hazards for the user.
With the help of a supervision unit the wiring errors may be detected immediately. Possible wiring errors are:

  • N and GND conductors are connected together,
    not only through the main ground bus.
  • N and GND conductors have been swapped somewhere in the electrical system
  • A load has been connected between a phase conductor and the ground
  • A device is grounded through its installation parts
  • Neutral to neutral wiring errors (if the measurement is close to the load)

ON-LINE detection of insulation faults

The most usual reason for a fire risk is the damage in the cable insulation. This may occur due to overloading, excessive moisture, insulation deterioration, mechanical stress, etc. The supervision equipment detects an incipient insulation damage as the fault current value rises. The Superintend system detects an arcing fault before a fuse or a circuit breaker operates.

Supervision of the integrity of a distribution network

Leakage and stray currents cause potential differences and disturbance voltages in computer and building management networks. These power disturbances are particularly harmful in data lines. If a partial or complete short circuit occurs between the N and G conductors, the electrical system operates as a four-conductor system. In this case the benefits of a five-conductor system are lost. Only by continuous supervision of a grounded electrical system, can the system be kept “clean”.

Measurement of small currents

With this Supervision Unit it is possible to measure small currents in the range of 5 mA to 10 A.


CONTINUOUS MONITORING OF ELECTRICAL INSULATION

Over time leakage current increases because the insulation begins to degrade. By continuous monitoring of leakage current, weakened insulation can be identified before the circuit breaker trips and production is shut down.

Sensitive monitoring unit with digital leakage current reading.
Monitoring is from 5 mA to 10 A and alarm settings from 10 mA to 9,5A.
Time delay settings are from 0.14 sec to 60 sec
Power input to monitoring unit is 24 V AC/DC.
Monitoring unit has a max/min ground leakage current memory.


AN EXAMPLE OF WIRING VRE-10 UNIT


DISPLAY
DISPLAY EXAMPLES
Measuring normal display. Continuous measuring.
Range selection mA/A works automatically.
Display indicates 290 mA
Measuring range is 5 mA to 9.99 A.
SETTINGS
Setting of alarm limit 10 mA...9.50 A
Steps 10, 20... 90 mA
100, 125... 975 mA
100, 1.25... 9.50 A
Setting of alarm delay: 0, 1, 2...
10.15...60 s
”0” delay is max 140 ms
SELF TESTING
VRE-10 tests itself automatically every 90 seconds.
Fault indication: power break (shown on the display)
or
Fault indication: low test current.
The fault could be e.g. loss of measuring wire.
ALARM DISPLAY
Alarm limit has been exceeded.
The duration of the alarm has been shorter than the set delay.
Current alarm.
The duration of the alarm has been longer than the set delay.
Equipment fault.
The faults can be scrolled in the fault record.
MIN/MAX CURRENT MEMORY
Display of max current (491mA).
Display of min current (97mA).
Max/min current memories can be reset. Active equipment faults stay in memory until the fault has been fixed and acknowledged.


CONNECTIONS OF VRE-10

Terminals

1-2 Operating voltage
18 to 30 VDC or 18 to 24 VAC. When using DC voltages the supervision unit automatically adjusts the polarity of the source voltage. There is a device-specific fuse inside the case (T160mA), time-lag type.

3-4 Operating voltage looping
1 >>> 3 and 2 >>> 4

5-6 Remote acknowledgement
Requires pulse: 5 to 30 VDC or 5 to 24 VAC. Minimun duration 100 ms. Positive voltage to terminal 5 and negative to terminal 6.

7-8 Serial interface.
The serial communication interface terminals are shown in figure. The direction of the current is 7>>>8, Umax 30 VDC I max. 40 mA

9-11 Alarm relay connection
The alarm relay terminals and contacts are shown in figure. The relay is shown deenergized (no alarms or all alarms have been acknowledged). Max 60 VDC 1A / 120 VAC 1A


INTERCONNECTION CABLES

WIRING WITH STANDARD PLUG-IN MEASURING CABLES:

IN THE USA 600 V, 90°C
IN THE OTHER COUNTRIES 1000 V, 90°C


WIRING WITH INSTRUMENTATION CABLE

Installation with screw terminals

The VMPH-2F signal cable for the current transformer is 2-feet long (0.6 m). One end of the cable has a plug connector (for VRE-10 unit) and the other end has four color-coded wires for connection to screw terminals on the instrumentation cable.

Installation with plug connector

The VMP-2F signal cable for the current transformer is also two-feet long (0.6 m). Both ends of the cable have plug connectors. The VMPA-1 (one channel model) and VMPA-4 (four channel model) are adapters for VMP-2F signal cable. The adapter has socket(s) for VMP-2F signal cable and screw terminal(s) for the instrumentation cable.


TECHNICAL SUMMARY OF GROUND
FAULT MONITOR VRE-10

Supply voltage 18 to 24 VAC or 18 to 30 VDC
Power burden 1.5 VA
Operating temperature 32 to 130°F (0 to 55°C)
Storage temperature 0 to 160°F (-20 to 70°C)
Humidity less than 95%, non condensing
Dimensions 3.4 inches wide x 4.4 inches deep x 2.6 inches high
(87 mm x 113 mm x 66 mm)
Weight 0.5 lb (220 g)

Measuring characteristics
Channels 1
Measuring range 5 mA to 9.99 A
Display resolution I > 1 A to 10 mA I < 1 A to 1mA


Accuracy of current transformers:
VMI-xx (closed core) + 5 % accuracy + 1-2 dgt
VMIK-xx (split-core) + 10 % accuracy + 1-2 dgt
VMIC(K)-xx (window type) +20 % repeatability +5 %
Setup
- alarm range 10 mA to 9.5A
- alarm time delay 0 to 60 seconds (with no delay the response time of the relay is 140 ms)
- hysteresis 0 to 90% of the alarm level

Alarm Relay
relay contacts single pole double throw (spdt)
I (maximum) max 1.25 A
I (switching current) max 1.0 A at 120 V AC or 60 V DC resistive load
P (switching power) 60 VA/ max 24 Watts

Sum Current Transformers
Thermal limiting current, 1 second 100 kA
Dynamic limiting current, peak value 250 kA
Continuous thermal limiting sum current 100 A

For measurements and weight see page ”Sum Current Transformers”


VRE-10 UNIT DIMENSIONS